FANUC Robot Repair: SRVO-021 Group and Axis Checks
Learn how to document FANUC SRVO-021 correctly, confirm the affected group and axis, and separate servo-enable evidence from an assumed amplifier failure.

In this article
FANUC robot repair for SRVO-021 should begin with accurate fault identification, especially the affected Group and Axis. On an R-30iB Mate or R-30iB Mate Plus controller, SRVO-021 SRDY OFF means that HRDY is ON while SRDY remains OFF, no other alarm explains the state, and the servo amplifier magnetic contactor did not turn on as commanded. This definition identifies a servo-enable condition; it does not by itself prove that the servo amplifier is damaged. Record the complete alarm, controller and robot identifiers, and operating conditions before any diagnostic action.
Symptoms and Scope
The documented scope for this procedure is FANUC Robot series R-30iB Mate and R-30iB Mate Plus controllers covered by FANUC America Corporation manual B-83525EN/07. Connector locations, cabinet layouts, and inspection procedures depend on the installed controller configuration and matching manual version. The same alarm text should not be transferred automatically to another FANUC controller generation without checking its applicable documentation.
SRVO-021 may leave the robot unable to servo on, but the visible symptom can have several possible explanations. An earlier alarm, an instantaneous power interruption, configuration-specific connection issues, an emergency-stop unit condition, or a servo amplifier problem may be involved. The alarm alone cannot independently distinguish these possibilities or justify amplifier replacement.
Information to Record First
Before resetting or inspecting the system, capture the following information:
Complete alarm code and full text
Date and exact time
Faulted axis
Robot position or posture
Program step or motion
Actual speed and load condition
Reset result
Time until recurrence
Related power, communication, or feedback alarms
For this fault, also record the controller model, robot model, Group and Axis, alarm history or full event log, and any available servo-amplifier label information. HRDY and SRDY status may be useful when available from the diagnostic screen or maintenance records, but personnel should not perform an unsafe intervention merely to obtain these states.
Safety and Preparation
Place the cell in a safe condition under the siteâÂÂs lockout, isolation, and stored-energy procedures. Only suitably competent personnel should inspect the controller, emergency-stop circuit, or servo hardware. Do not alter safety settings, bypass an interlock, or perform an energized measurement unless the applicable FANUC documentation and site procedure specifically authorize that work. Connector names and inspection points must be confirmed against the actual controller configuration rather than assumed from a different cabinet.
Diagnostic Sequence
- Confirm the complete fault record. Input the full SRVO-021 text, Group, Axis, timestamp, and alarm history. Inspect whether another alarm occurred earlier or at the same time. If an earlier alarm explains the servo state, diagnose that condition first and retain SRVO-021 as a consequence unless later evidence shows otherwise.
- Confirm the controller and robot identifiers. Check the controller model, robot model, axis arrangement, and installed hardware labels. The documented manual scope is limited to R-30iB Mate and R-30iB Mate Plus controllers. If the installed equipment differs, stop using configuration-specific instructions until the correct manual is identified.
- Confirm the HRDY and SRDY relationship. The relevant condition is HRDY ON while SRDY remains OFF, with no other alarm explaining the state. If the diagnostic status does not match this condition, the observed problem may not be the documented SRVO-021 state, and the complete alarm history requires review before proceeding.
- Inspect configuration-specific connections. With the controller safely isolated as required, inspect the applicable connectors, harnesses, and visible terminals for loose engagement, damage, contamination, or evidence of service disturbance. The exact connection points depend on the installed configuration. Do not infer a connector fault from the alarm alone, and do not use connector names from another controller layout without verification.
- Check for an instantaneous power interruption. Review the event timing, machine records, and site power information for an interruption that coincided with the alarm. This step concerns whether an instantaneous power interruption occurred. Do not broaden the conclusion to voltage fluctuation or other power conditions without separate evidence. If an interruption is supported, follow the applicable restart and power-quality investigation procedure before evaluating replacement parts.
- Evaluate the emergency-stop unit and servo amplifier according to the applicable FANUC maintenance manual. The decision input is the verified alarm state, earlier-alarm record, connection inspection, and power-interruption evidence. A clean external inspection does not prove either unit is functional or failed. Professional testing, repair, or replacement should be considered only after the equipment configuration and evidence support that decision.
How to Distinguish Similar Causes
A prior alarm that identifies a safety, power, or connection condition should take diagnostic priority over the resulting SRVO-021. A matching HRDY/SRDY state with no earlier alarm confirms the documented symptom, but it still does not isolate the emergency-stop unit from the servo amplifier. Motor, feedback-related, or mechanical branches should be considered only when another earlier or associated alarm supports them. Do not expand the investigation to those systems solely because the robot will not servo on.
When Repair or Replacement May Be Considered
A repair or replacement decision requires the exact controller configuration, component label, model, part number, hardware revision, and connector layout. Any replacement servo hardware must be matched to the installed system and verified against the applicable FANUC documentation. The FANUC R-30iB servo amplifier repair information may be relevant when the installed component is positively identified, but SRVO-021 alone is not sufficient evidence that the amplifier requires replacement. ZHB is an independent industrial robot inspection, repair, and maintenance service provider that also supplies parts to overseas customers; manufacturer authorization should not be assumed.
Verification After Repair or Replacement
After corrective work, verify that the alarm history is documented, the safety circuit is restored according to site procedure, and the controller recognizes the intended hardware configuration. Confirm the expected HRDY and SRDY states before controlled operation. Any motion observation must be performed only by suitably competent personnel under controlled conditions, in accordance with the applicable manufacturer operating information and site safety procedure. Do not repeatedly cycle or reproduce the fault when doing so could increase equipment risk.
Information Required for a Repair Inquiry
For a focused repair assessment, provide the controller model, robot model, complete SRVO-021 code and text, Group and Axis, full event log, alarm time, component label, fault conditions, connector photographs, servo-amplifier label, and clear photographs of the cabinet and relevant hardware. Include HRDY and SRDY only when those states can be obtained safely from the diagnostic screen or existing maintenance records.
Sources and Update Information
Technical reference: FANUC America Corporation, FANUC Robot series R-30iB Mate/R-30iB Mate Plus Controller Maintenance Manual, B-83525EN/07, SRVO-021 SRDY off, page 73. An accessible copy is hosted by Haas Automation at https://www.haascnc.com/content/dam/haascnc/en/service/reference/fanuc-manuals/Fanuc%20Robot%20Series%20R-30iB%20Mate%20%2B%20Mate%20Plus%20Maintenance%20Manual.pdf.
Conclusion
SRVO-021 is a servo-readiness condition that requires evidence-led diagnosis. Correctly recording Group and Axis, checking for earlier alarms, confirming HRDY and SRDY, reviewing configuration-specific connections, checking for an instantaneous power interruption, and then evaluating the emergency-stop unit and servo amplifier helps prevent an unsupported component diagnosis.