FANUC Robot Repair: SRVO-021 After Power Interruption
Diagnose FANUC SRVO-021 after an instantaneous power interruption without assuming servo amplifier failure or replacing parts prematurely.

In this article
FANUC robot repair for SRVO-021 SRDY OFF should begin by documenting the complete alarm, Group, Axis, event sequence and controller configuration. For the supported R-30iB Mate and R-30iB Mate Plus scope, SRVO-021 means HRDY is ON while SRDY remains OFF, no other alarm explains the state, and the servo amplifier magnetic contactor did not turn on as commanded. An instantaneous power interruption is one documented condition to investigate, but the alarm alone does not prove that the servo amplifier or another component is damaged.
Symptoms and Scope
This article addresses SRVO-021 SRDY OFF on FANUC robots using R-30iB Mate or R-30iB Mate Plus controllers covered by maintenance manual B-83525EN/07. Connector locations, wiring arrangements and diagnostic procedures depend on the installed controller configuration. Other FANUC controller families require their corresponding maintenance documentation.
The relevant symptom is a failure to reach the expected servo-ready state. The alarm does not independently identify a failed amplifier, emergency-stop unit, cable or connector. It also does not justify expanding the investigation to the motor, feedback-related components or mechanical system unless an earlier or associated alarm supports that branch.
Information to Record First
Preserve the evidence before clearing alarms or cycling power. The first alarm in the event sequence may explain why SRDY remained OFF, while SRVO-021 may describe a later controller state.
Complete alarm code and full text: Record SRVO-021 SRDY OFF exactly as displayed, including Group and Axis.
Date and exact time: Record when the event occurred.
Faulted axis: Record the indicated axis without assuming that the axis hardware caused the event.
Robot position/posture: Record the position when the alarm appeared.
Program step or motion: Record whether the robot was starting, stationary or executing a program.
Actual speed and load condition: Record the available operating information.
Reset result: Record whether the alarm cleared and whether servo enable was restored.
Time until recurrence: Record whether the event returned and under what conditions.
Related power, communication or feedback alarms: Preserve all earlier and associated entries.
Safety and Preparation
Place the robot and connected equipment in a controlled state according to the site lockout procedure and the applicable FANUC safety information. Do not open the controller, reseat internal connections or inspect energized assemblies unless the work is assigned to suitably competent personnel using the required protective measures.
Do not repeatedly cycle power or command motion merely to reproduce an intermittent event. Observation during motion, when genuinely necessary, must be conducted by competent personnel under controlled conditions and in accordance with manufacturer operating information and site safety procedures.
FANUC Robot Repair Diagnostic Sequence
1. Confirm the equipment scope. Record the robot model, controller model, installed options and servo-amplifier label. If the controller is not an R-30iB Mate or R-30iB Mate Plus, obtain the maintenance manual for that controller before applying model-specific procedures.
- Review the complete alarm history. Identify any alarm recorded before SRVO-021. If an earlier alarm explains why the servo-ready state was not achieved, follow the diagnostic branch for that alarm first. If no other alarm explains the state, continue with the SRVO-021 sequence.
- Confirm the ready-state information. From the diagnostic screen or existing maintenance records, determine whether HRDY was ON while SRDY remained OFF. If that condition cannot be confirmed, preserve the available records and avoid treating SRVO-021 as proof of a specific component fault.
- Inspect configuration-specific connections. With power isolated and the stored-energy precautions in the applicable manual completed, qualified personnel may inspect the connections relevant to the installed configuration for looseness, damage or an incorrect post-service connection. Do not apply connector names or locations from a different controller arrangement. Photographs taken before disturbing a connection can support later review.
- Check for an instantaneous power interruption. Compare the exact alarm time with facility power records, machine logs and reports from adjacent equipment. A matching interruption is relevant evidence in the documented diagnostic sequence. An unverified assumption about broader power behavior is not a diagnosis, and absence of a facility record does not by itself establish component failure.
- Evaluate the emergency-stop unit and servo amplifier. If no earlier alarm explains the event, the ready-state condition is confirmed, connections match the installed configuration and the power-interruption check is inconclusive, evaluate these assemblies according to the applicable FANUC manual. Professional bench inspection may be appropriate when the servo amplifier remains suspect, but repair or replacement should follow evidence rather than the alarm name alone.
When Repair or Replacement May Be Considered
A component decision should account for alarm history, inspection results, recurrence conditions and configuration. Before sourcing a servo amplifier, match the exact model, part number, hardware revision and connector layout. A visually similar unit is not sufficient evidence of compatibility.
For an identified R-30iB servo-amplifier issue, the FANUC R-30iB servo amplifier repair page at https://autonews.best/products/fanuc-r-30ib-si-fu-qi-ji-xiu provides a relevant service route. This link does not establish that the amplifier caused SRVO-021; the diagnostic sequence must support that conclusion first.
Information Required for a Repair Inquiry
ZHB is an independent industrial robot inspection, repair and maintenance service provider that also supplies parts to overseas customers. For an SRVO-021 inquiry, provide the controller model, robot model, Group and Axis, full event log, alarm time, connector photographs and servo-amplifier label. Include HRDY and SRDY information when it can be obtained from the diagnostic screen or maintenance records. Clear photographs should show complete labels and the installed connector arrangement without requiring unsafe access.
Verification After Repair or Maintenance
After approved work, confirm that guards, covers, grounding provisions and inspected connections have been restored. Review the alarm history, verify that the controller reaches the expected ready state and perform the manufacturer-specified restart checks. Any controlled motion verification must use an appropriate operating mode, restricted access and site-approved speed and load conditions. Record the result and retain the replaced or repaired component identification in the maintenance history.
A successful reset alone is not sufficient closure for an intermittent event. Compare the restart result with the original fault conditions and monitor for recurrence during authorized production verification. Do not deliberately recreate a power interruption to prove that the repair succeeded.
Common Diagnostic Mistakes
Common errors include replacing the servo amplifier solely because SRVO-021 mentions the magnetic contactor state, overlooking an earlier alarm, omitting Group and Axis information, and using connector instructions from the wrong controller configuration. Another mistake is expanding immediately into motor, feedback or mechanical troubleshooting without an associated alarm directing the investigation there.
Sources and Update Information
FANUC America Corporation, FANUC Robot series R-30iB Mate/R-30iB Mate Plus Controller Maintenance Manual, B-83525EN/07, SRVO-021 SRDY off, page 73. The accessible PDF copy is hosted by Haas Automation: https://www.haascnc.com/content/dam/haascnc/en/service/reference/fanuc-manuals/Fanuc%20Robot%20Series%20R-30iB%20Mate%20+%20Mate%20Plus%20Maintenance%20Manual.pdf
Conclusion
SRVO-021 following an instantaneous power interruption requires evidence-based triage. Record the full event sequence, confirm Group and Axis, identify any earlier alarm, verify HRDY and SRDY, inspect only configuration-specific connections, check the interruption record, and then evaluate the emergency-stop unit and servo amplifier under the applicable manual. This order limits unnecessary part replacement while preserving the information needed for a defensible repair decision.